Wire Gauge & Breaker Calculator

Enter the appliance power, the cable run and how it is installed to get the working current, the copper wire cross-section, the breaker rating and the voltage drop at the far end.

Wire size is decided by current, not by habit. Undersized cable heats up, the breaker trips on a hot day, and the light at the far end dims when the kettle goes on. Enter the appliance, the run and how the cable is installed; the page returns the current, the cross-section, the breaker and the voltage drop.

Circuit details

Single phase 220 V. Results update as you type.

Working current –
Copper wire –
Breaker –
Voltage drop –

–

Copper cable capacity (in conduit)

Cross-sectionCurrentPower at 220 V
1.5 mm²14 Aabout 3.1 kW — lighting, small sockets
2.5 mm²19 A—
4 mm²25 Aabout 5.5 kW — kitchen, water heater
6 mm²32 A—

How to read the result

  • The breaker protects the cable, not the appliance. A 32 A breaker on 2.5 mm² cable lets the wire overheat before the breaker ever trips.
  • Derating matters: the same cable carries less in conduit (×0.8) and less again under insulation (×0.7).
  • Voltage drop is about length: 2.5 mm² is fine at 10 m and marginal at 40 m for the same load.
  • For fixed appliances above 3 kW, run a dedicated circuit back to the distribution board instead of sharing a ring.
  • Aluminium cable needs a larger cross-section than copper; this calculator is for copper only.

Practical notes

  • Air conditioners and motors draw a starting surge of 3–5 times the running current; use the inductive option and do not size to the wire limit.
  • Never run a 16 A load on a 10 A socket. The plug and the socket have their own rating, separate from the cable.
  • Keep the breaker rating at or below the cable capacity after derating, and above the appliance current.
  • For long garden or garage runs, check the drop first — it often decides the cable size before the current does.

Four common mistakes

  • Choosing cable by the breaker instead of the load, so the protection never matches the wire.
  • Ignoring derating and using the free-air ampacity for a cable buried under insulation.
  • Sharing one 2.5 mm² circuit between a kitchen, a heater and a washing machine.
  • Joining cables with tape inside a wall; joints belong in accessible boxes.

Guidance for planning only. Local wiring regulations, cable type and installation conditions govern the final choice; have fixed wiring installed and inspected by a licensed electrician.